Model
TR-Spy Mark II
Fully Automatic Three Phase Transformer
Turns-Ratio Meter |
|
|
Description |
The TR-Spy Mark II is a fully enhanced automatic
three phase turns ratiometer. The system is easy to use and
has many useful features such as the large memory base, external
control for tap changer testing, and an automatic voltage
level detection test.
- There are over 1,300 memory locations available to allow
the end-user to store over 100 complete transformer tests.
That means you can store a three phase transformer with
32 taps, all of the nameplate data, operator, location tested
etc… in one storage location. This data can be accessed
later for downloading and report generation. The system
can also deliver more current for the testing of CTs.
- The test set has 4 test voltage levels: 1, 10, 40 &
100 V and Automatic mode, which is used for most transformers
to allow maximum accuracy at an optimum output power level.
The system can be set up to test a transformer with multiple
taps with the press of one button and save the data automatically.
- The TR-Spy Mark II is a microprocessor based Single and
Three Phase Transformer Turns Ratio Test set. This system
is designed to give highly accurate readings in the field
with laboratory precision. It is the most accurate system
available.
|
|
| |
| Specifications |
|
Model: TR-Spy Mark II
Size: L: 18. 5 in. (470mm) W: 14.6 in.
(371mm) H: 7.5 in. (190mm)
Weight: 18 lbs. (8.2 kg)
Input Power: 100 to 250 VAC 50 / 60 Hz
Autoranging. Fuse: 2 Amp
Test Voltage: User selectable: 100, 40,
10, 1 VAC, and Auto at 1 ampere
Panel Display: LCD graphic with back lighting
Front Panel : Sealed, Piezo-electric actuation
Interface: 9 pin RS232 serial / 25 pin
standard centronics parallel
Memory Storage: Internally
stores more than 1,300 locations in memory (100 complete)
-
|
|
|
Measurement Parameters |
|
Voltage/Turns Ratio Range: 0.8 ... 13,000
Resolution: 5 Digits |
|
|
Accuracy |
|
|
|
|
|
Range 0.8 .... 2000 ±0.08% with 100 and 40 Volt, ±0.15%
with 10 Volt
Range 2001 .... 4000 ±0.15% with 100 and 40 Volt, ±0.22%
with 10 Volt
Range 4001 .... 13,000 ±0.3% with 100 and 40 Volt, ±0.5%
with 10 Volt |
|
|
|
|
|
|
|
Current
|
|
Phase
Angle |
|
|
|
|
|
| Range
: |
|
0 ... 1 Ampere |
|
±
90 Degrees |
|
|
|
|
|
| Accuracy: |
|
±
0.001 Ampere |
|
±
0.05 Degree |
|
|
|
|
|
| Resolution:
|
|
0.0001 Ampere |
|
0.01 Degree |
|
|
|
|
|
Temperature: Operating: - 10°
C to 60° C Storage: - 40° C to 70° C
|
|
|
Features |
|
•
Automatic measurements of Voltage/Turns Ratio, Current and
Phase displacement
• Internal storage for 100 complete
test results (greater than 1,300 memory locations)
• Single push button operation
• Single hook up to the transformer
• Ratio testing from 0.8 to 13,000
turns
• Five test voltage ranges: 1 V, 10V,
40V, 100V and Automatic
• Displays deviation from a nominal
ratio
• Graphical tap changer display
• Load on test object < 0.05 VA
• Enhanced, heavy-duty protection
circuitry
• Centronics (Parallel) interface
and RS232 (Serial) interface
• Five year standard warranty
|
|
Standard Accessories |
• Cable carrying bag with shoulder strap
• TR-Spy Mark II shoulder strap
• H & X measuring leads –
multicolored, 3.5 Meters in length, each
• Extension cables, Qty. 2 – Red,
10 Meters in length, each
• Power cord – 15 ft. in length
• RS-232 cable (for use when upgrading
firmware, downloading stored results, or remote
operation)
• Operation manual
• Test Certificate
|
|
|
Optional Accessories |
SM201
External test switch for Tap changer testing.

-
SM202
Extended cable lengths (user specified in 32 foot increments).

-
SM203 - Custom clamping
devices (user specified).
SM204
- External portable power supply.
-
- SM206
- Test with three-phase voltage.
SM207
- Verification box

|
| |